Welcome to the LX Transformer Support Section. Here you will find instructions to install and program your landscape lighting controller. Proper installation and setup will allow you to take full advantage of all the features the LX Transformer has to offer.
![]()
Section Menu
Support Topics
Components
-
Components
Control Buttons Mode Selector Arrow Up and Down - Increases value or decreases value Enter Button Left Row Auto - Program is running Set Time - Set
Owners Manual
Installation
-
Locating the transformer
Locate transformer(s) in a well-ventilated area away from direct irrigation spray and central to where the majority of the lighting fixtures will be installed. The goal is to
-
Running cable to fixtures
Once the transformer has been installed and all fixture locations determined, the next step is to run the correct size cable from the transformer to the fixtures while providing
-
Loads per Cable
CABLE STATS Low voltage lighting systems are typically installed using UF (underground feeder) rated stranded cable. The most common cable used is referred to as 12/2 stranded
-
Linking Transformers
The LX Transformer can be controlled from another transformer via the 1–24 volt EXTERNAL connection. If you have multiple transformers on a single site, a PRIMARY transformer
-
Tools for installation
Receptacle Tester This tool tells you whether or not the 120 volt receptacle you are plugging the LX Series Transformer into is wired properly. Follow the tool manufacturers
Programming
-
System Time
To set the main system clock, follow the instructions below.
-
Program On Time
Programs are designated by a letter from A-F and must have an On Time with days of the week selected as well as an Off Time.
-
Program Off Time
After choosing a Program letter and setting its On Time(s) the Off times must be set for the same program selected by pressing the Mode selector button to initiate the setting mode
-
Manual Mode
To manually turn on fixtures for a designated period, follow the instructions below.
-
Turning System Off
To turn off the LX power controller, navigate to the OFF setting using the MODE button and wait 3 seconds. The lights will turn off. If you leave the system in the OFF mode, they
Troubleshooting
-
Troubleshooting Overview
Problem No power at plug Cause Tripped breaker or GFCI Solution Reset circuit
-
Checking Voltage Overview
Using a digital voltmeter allows you to take important voltage readings at the transformer, at each fixture and at the receptacle the transformer will be plugged into. Dial the
-
Incoming Power Testing
The quickest way to see if the Transformer is receiving power is to plug a working lamp or radio into the outlet to see if outlet is providing power. If unit is hardwired to power
-
No Power at Fixtures
The first test to perform will determine if power is passing through the Transformer to the low voltage taps. Turn your volt meter on and place one of the probes on the lug
-
Hard Reset
Electrical surges and voltage spikes can cause anomalies in the face pack of the transformer. To return the face pack to its original setting, complete the reset procedure listed
-
Photocell Not Working
The LX lighting transformers are equipped with a photocell on the outside lower right of the unit. The LX can be programmed to turn lights ON at dusk and turn OFF at dawn. If the
-
Internal fuse replacement
If the LX transformer does not power on THE LOW VOLTAGE TERMINALS when plugged into a working outlet, the internal fuse may need to be replaced. NOTE: The front panel will still
-
Circuit overload
If the amperage load on any given common lug exceeds the transformer capacity, the circuit breaker will trip and the display will read ”Err” (Error). Test the amperage load on all
-
Lamp Replacement
A common mistake made by many is to replace existing lamps with lamps of higher wattage than those originally installed. Example: If you have an FX system with a PX-600 watt
FAQs
-
Suggested Maintenance
Periodic system maintenance is required to keep your FX lighting system operating at peak performance. Practicing these maintenance suggestions will lengthen the life and enjoyment
-
14 Volt Tap
Underwriting Laboratories (UL), the independent safety testing lab for all things electrical, allows Low Voltage Transformer manufacturers like FX to produce transformers with up
-
Upgrading Transformer
Upgrading the LX face panel with the DX version (part number DX-FP) will allow you to have all the great features of the DX transformer in just a view simple few steps. For more